Cascading Multiple Digi RPM Units
136 Chapter 14
Cascading Multiple Digi RPM Units
The Digi RPM power controllers can be cascaded when used with the Digi CM
unit.
The DIP switches on the front panel of the Digi RPM allow configuring unique
identities (ID) to the Digi RPMs so they can be identified. In a cascaded
environment each unit has to be configured to a unique ID.
To cascade the Digi RPM units, connect a serial port of the Digi CM unit to the
Console Port of the first Digi RPM unit using a straight-thru cable. Connect the
“Cascade” Port of the first Digi RPM unit to the “Console” Port of the second.
Following an example of two cascaded Digi RPM units connected to a Digi CM
unit.
Please note that the ID for the first unit is set to 0 and for the second unit it is
set to 1.
The next table shows all possible IDs that can be configured on the Digi RPM.